JCM 114 Henderson NC 24 inch Asbestos Cement Pipe

Problem Leaking Asbestos Cement Coupling Line Content: Potable Water Pressure: 150 PSI

A/C Coupling OD: 33.14” A/C Coupling Length: 10-1/8”

A/C Spigot OD – diameter varies in repair area:

Minimum: 28.53” Maximum: 28.85”

At right – a simple hand drawing of the leaking coupling and the measured dimensions of the pipe around the coupling. These dimensions were used to fabricate the repair fitting – giving it a custom fit.

Powered by